I/O Modules
Q.bloxx A101
2 universal analog input channelsvoltage, current, resistance, potentiometer, Pt100, Pt1000, thermocouples, measuring bridges, IEPE sensorsFast high accuracy digitalization
24 bit ADC, 100 kHz sample rate per channel
1 digital in or output per channel
input: state, tare, memory reset
output: state alarm, threshold
Signal conditioning
16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Q.bloxx A102
1 analog input channelmeasuring bridge (full, half, quarter), IEPE-sensors, voltage, current1 analog output
voltage ±10 V and current 0 up to 25 mA selectable, 100 kHz
Fast high accuracy digitalization
19 Bit ADC - SAR (without delay time), 100 kHz sample rate
4 digital inputs, 2 digital outputs
input: state, tare, memory reset
output: state alarm, thresh hold
Signal conditioning
16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Q.bloxx A103
8 galvanic isolated input channelsdifferential voltage, current via shunt connectorIsolation voltage 100 VDCHigh accuracy digitalization
24 bit ADC, 100 Hz sample rate per channel with 8 active channels, 100 Hz sample rate per channel
2 digital in and 2 outputs
input: state, tare, memory reset
output: state alarm, thresh hold
Signal conditioning
linearization, digital filter, average, scaling, min/max storage, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Accuracy class 0.01
Q.bloxx A104
8 galvanic isolated input channelsthermocouples and voltages in the range of ±80 mV Isolation voltage 100 VDCCold junction compensation
good thermal coupling by means of cold junction compensation per connector
Dynamic linearization
optimized positioning of the interpolation points within the
selected range, type B, E, J, K, L, N, R, S, T, U
High accuracy digitalization
24 bit ADC, 100 Hz sample rate per channel with 8 active channels, 100 Hz sample rate per channel
Signal conditioning
digital filter, average, scaling, min/max storage, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Accuracy class 0,01
Q.bloxx A105
High accuracy
Deviation max. 0.05°C, Temperature influence 0.02/10K
4 input channels
Pt100 or resistance in 3- or 4- wire technique
High accuracy digitalization
24 bit ADC, 10 Hz sample rate per channel
Signal conditioning
linearization, digital filter, average, scaling, min/max storage, arithmetic, alarm
Galvanic isolation
channel to channel to power supply and to interface Isolation voltage 500 VDC
Q.bloxx A105CR
4 galvanically isolated input channels for cryogenic sensors
e.g. type Cernox, type TVO, input range selectable 6500 Ω or 20000 Ω
Sensor excitation 7.5 μAeff only
Avoids self-heating of the sensor
Individual linearization of the sensor characteristics
Sensor specific linearization by using 32 nodes and archive in a sensor data file. Import of manufacturers calibration data
High accuracy digitalization
24 bit ADC, 10 Hz sample rate per channel
Signal conditioning
linearization, digital filtering, averaging, scaling, min/max storage, arithmetic, alarm
Galvanic isolation
channel to channel to power supply and to interface, isolation voltage 500 VDC
Q.bloxx A106
2 analog input channels
Strain gage and inductive measuring bridges (full, half, quarter), LVDT, RVDT
DC and carrier frequency (CF) principle
DC excitation, 600 Hz CF excitation, 4.8 kHz CF excitation for bridges
1 analog output per channel
Voltage ±10 V, 10 kHz
Fast high accuracy digitalization
24 bit ADC, 10 kHz sample rate per channel
1 digital in or output per channel
input: state, tare, memory reset
output: state alarm, thresh hold
Signal conditioning
16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Q.bloxx A107
4 universal analog input channels
voltage, current, resistance, potentiometer, Pt100, Pt1000, thermocouples, measuring bridges
Fast high accuracy digitalization
24 bit ADC, 10 kHz sample rate per channel
Signal conditioning
16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface
Q.bloxx A108
8 galvanic isolated input channels
differential voltage, current via shunt connector Isolation voltage 100 VDC
Fast high accuracy digitalization
24 bit ADC, 10 kHz sample rate per channel with 8 active channels
2 digital in and 2 outputs
input: state, tare, memory reset
output: state alarm, thresh hold
Signal conditioning
linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Accuracy class 0,01
Q.bloxx A108-100V
8 galvanic isolated input channels
differential voltage ±100 V, isolation voltage 500 VDCHigh accuracy digitalization
24 bit ADC, 10 kHz sample rate per channel
2 digital outputs
state, alarm, treshold
Signal conditioning
linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
channel to channel to power supply and to interface Isolation voltage 500 VDC
Accuracy class 0,01
Q.bloxx A109
4 galvanic isolated analog output channels
voltage ±10 V, current 4…20 mA selectable Isolation voltage 500 VDC
DAC-resolution 16 bit
100 kHz with 1 channel, 10 kHz with 4 channels
4 digital inputs and 4 digital outputs
configurable as 2 counter, 2 frequency, or 2 PWM inputs, 2 frequency or PWM output, state in or output
Frequency in and outputs
frequency measurement up to 1 MHz (Chronos method), frequency output up to 10 kHz
Counter
For/backward counter, quadrature counter with reference zero recognition (reset/enable), up to 1 MHz
PWM in and output
measurement of duty cycle and frequency, output with variable frequency and/or duty cycle
Outputs freely scalable
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Q.bloxx A111
4 galvanic isolated analog input channels
IEPE sensors, voltages
Fast high accuracy digitalization
24 bit ADC, 100 kHz sample rate per channel
Signal conditioning
16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
channel to channel to power supply and to interface isolation voltage 500 VDC
Q.bloxx A123
4 galvanically isolated input channels
Voltages at high potential, ranges 100 mV, 1 V, 10 V
Insulation voltage 1200 VDC
short-term 5000 VDC
Fast high accuracy digitalization
24 bit ADC, 50 kHz sample rate per channel with 4 channels, 100 kHz sample rate per channel with 2 channels
Signal conditioning
16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Q.bloxx A124
4 galvanically isolated input channels
for non-insulated thermocouples at high potential
Insulation voltage 1200 VDC
short-term 5000 VDC
Cold junction compensation
Dynamic linearization
Optimum positioning of interpolation points in selected range, types B, E, J, K, L, N, R, S, T, U
High accuracy digitalization
24 bit ADC, 10 kHz sample rate per channel
Signal conditioning
digital filter, average, scaling, min/max storage, arithmetic, alarm
Q.bloxx A127
4 voltage input channels
2 inputs for voltage measurement measuring ranges ±40 V, ±120 V, ±400 V, ±1200 V
2 inputs for current measurement via shunt resistors measuring ranges ±80 mV, ±240 mV, ±800 mV, ±2400 mV
Fast high accuracy digitalization
24 bit ADC, 50 kHz sample rate per channel with 4 channels, 100 kHz sample rate per channel with 2 channels
Signal conditioning
linearization, digital filter, average, scaling, min/max storage, RMS, alarm
Galvanic isolation
channel to channel to power supply and to interface isolation voltage 1200 VDC / 858 VACrms test voltage 5 kVDC over 1 minute
Q.bloxx A128
4 galvanically isolated input channels
Voltages, ranges 40 V, 120 V, 400 V, 1200 V
Insulation voltage 1200 VDC
short-term 5000 VDC
Fast high accuracy digitalization
24 bit ADC, 50 kHz sample rate per channel with 4 channels, 100 kHz sample rate per channel with 2 channels
Signal conditioning
16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Q.bloxx D101
8 digital inputs and 8 digital outputs
configurable as counter, frequency, PWM and time inputs, frequency or PWM output, state in or output
State in and outputs
process- and host controlled
Frequency in and outputs
frequency measurement up to 1 MHz (Chronos method), frequency output up to 10 kHz
Counter
for/backward counter, quadrature counter with reference zero recognition (reset/enable), up to 1 MHz
PWM in and outputs
measurement of duty cycle and frequency, output with variable frequency and/or duty cycle
Time measurement
Q.bloxx D104
16 digital inputs
state, single or bit set, host controlled
Configurable threshold
TTL or high level (EN61131-2, Type1)
Short reaction time
10 µs per input
Galvanic isolation
of I/O-signals (2 groups x 8 inputs), to power supply and to interface Isolation voltage 500 VDC
Q.bloxx D105
16 digital outputs
state, single or bit set, host controlled
High possible load
30 VDC / 500 mA short circuit proof
Short reaction time
10 µs up to 1 ms per input
Galvanic isolation
of I/O-signals (2 groups x 8 inputs), to power supply and to interface Isolation voltage 500 VDC
Q.bloxx D107
6 configurable digital inputs
2 channels, each 3 differential or single-ended, frequency, counter, PWM, state
Adjustable threshold in 256 steps
Differential inputs in the range of -20 V up to + 20 V, Single-ended inputs in the range of 0 V up to +26 V
Frequency inputs
Frequency measurement up to 1 MHz (Chronos method), direction recognition
Counter
Up/down counter, quadrature counter with reference zero, up to 1 MHz
PWM inputs
Measurement of duty cycle and frequency, output with variable frequency and/or duty cycle
Galvanic isolation
Terminal 1, Terminal 2, power supply and interface Isolation voltage 500 VDC