Q.raxx A101
2 universal analog input channels
voltage, current, resistance, potentiometer, Pt100, Pt1000, thermocouples, measuring bridges, IEPE sensors
Fast high accuracy digitalization
24 bit ADC, 100 kHz sample rate per channel
1 digital in or output per channel
input: state, tare, memory reset
output: state alarm, threshold
Signal conditioning
16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Q.raxx A102
1 analog input channel
measuring bridge (full, half, quarter), IEPE-sensors, voltage, current
1 analog output
voltage ±10 V and current 0 up to 25 mA selectable, 100 kHz
Fast high accuracy digitalization
19 Bit ADC - SAR (without delay time), 100 kHz sample rate
4 digital inputs, 2 digital outputs
input: state, tare, memory reset
output: state alarm, thresh hold
Signal conditioning
16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Q.raxx A103
8 galvanic isolated input channels
differential voltage, current via shunt connector Isolation voltage 100 VDC
High accuracy digitalization
24 bit ADC, 100 Hz sample rate per channel with 8 active channels, 100 Hz sample rate per channel
2 digital in and 2 outputs
input: state, tare, memory reset
output: state alarm, thresh hold
Signal conditioning
linearization, digital filter, average, scaling, min/max storage, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Accuracy class 0.01
Q.raxx A104
8 galvanic isolated input channels
thermocouples and voltages in the range of ±80 mV Isolation voltage 100 VDC
Cold junction compensation
good thermal coupling by means of cold junction compensation per connector
Dynamic linearization
optimized positioning of the interpolation points within the selected range, type B, E, J, K, L, N, R, S, T, U
High accuracy digitalization
24 bit ADC, 100 Hz sample rate per channel with 8 active channels, 100 Hz sample rate per channel
Signal conditioning
digital filter, average, scaling, min/max storage, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Accuracy class 0,01
Q.raxx A105
High accuracy
Deviation max. 0.05°C, Temperature influence 0.02/10K
4 input channels
Pt100 or resistance in 3- or 4- wire technique
High accuracy digitalization
24 bit ADC, 10 Hz sample rate per channel
Signal conditioning
linearization, digital filter, average, scaling, min/max storage, arithmetic, alarm
Galvanic isolation
channel to channel to power supply and to interface Isolation voltage 500 VDC
Q.raxx A106
2 analog input channels
Strain gage and inductive measuring bridges (full, half, quarter), LVDT, RVDT
DC and carrier frequency (CF) principle
DC excitation, 600 Hz CF excitation, 4.8 kHz CF excitation for bridges
1 analog output per channel
Voltage ±10 V, 10 kHz
Fast high accuracy digitalization
24 bit ADC, 10 kHz sample rate per channel
1 digital in or output per channel
input: state, tare, memory reset
output: state alarm, thresh hold
Signal conditioning
16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Q.raxx A107
4 universal analog input channels
voltage, current, resistance, potentiometer, Pt100, Pt1000, thermocouples, measuring bridges
Fast high accuracy digitalization
24 bit ADC, 10 kHz sample rate per channel
Signal conditioning
16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface
Q.raxx A108
8 galvanic isolated input channels
differential voltage, current via shunt connector Isolation voltage 100 VDC
Fast high accuracy digitalization
24 bit ADC, 10 kHz sample rate per channel with 8 active channels
2 digital in and 2 outputs
input: state, tare, memory reset
output: state alarm, thresh hold
Signal conditioning
linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Accuracy class 0,01
Q.raxx A109
4 galvanic isolated analog output channels
voltage ±10 V, current 4…20 mA selectable Isolation voltage 500 VDC
DAC-resolution 16 bit
100 kHz with 1 channel, 10 kHz with 4 channels
4 digital inputs and 4 digital outputs
configurable as 2 counter, 2 frequency, or 2 PWM inputs, 2 frequency or PWM output, state in or output
Frequency in and outputs
frequency measurement up to 1 MHz (Chronos method), frequency output up to 10 kHz
Counter
For/backward counter, quadrature counter with reference zero recognition (reset/enable), up to 1 MHz
PWM in and output
measurement of duty cycle and frequency, output with variable frequency and/or duty cycle
Outputs freely scalable
Galvanic isolation
of I/O-signals, power supply and interface Isolation voltage 500 VDC
Q.raxx A111
4 galvanic isolated analog input channels
IEPE sensors, voltages
Fast high accuracy digitalization
24 bit ADC, 100 kHz sample rate per channel
Signal conditioning
16 virtual channels, linearization, digital filter, average, scaling, min/max storage, RMS, arithmetic, alarm
Galvanic isolation
channel to channel to power supply and to interface isolation voltage 500 VDC
Q.raxx A116
8 analog input channels for bridges
strain gauge bridges (full, half, quarter), 8 real parallel inputs, neither scanned nor multiplexed
Flexible Input
DC bridge excitation 2 V and 4 V
input range 1 mV/V and 5 mV/V
Fast high accuracy digitalization
24 bit ADC, 10 kHz sample rate per channel
Signal conditioning
linearization, digital filter, average, scaling, min/max storage, arithmetic, alarm
Shunt calibration signal per channel
Compatible with all Q.series modules
e.g. for displacement, temperature, counter, voltage, current, resistance, frequency, I/O
Galvanic isolation
channel to power supply and to interface Isolation voltage 500 VDC
Q.raxx D101
8 digital inputs and 8 digital outputs
configurable as counter, frequency, PWM and time inputs, frequency or PWM output, state in or output
State in and outputs
process- and host controlled
Frequency in and outputs
frequency measurement up to 1 MHz (Chronos method), frequency output up to 10 kHz
Counter
for/backward counter, quadrature counter with reference zero recognition (reset/enable), up to 1 MHz
PWM in and outputs
measurement of duty cycle and frequency, output with variable frequency and/or duty cycle
Time measurement
Q.raxx D104
16 digital inputs
state, single or bit set, host controlled
Configurable threshold
TTL or high level (EN61131-2, Type1)
Short reaction time
10 µs per input
Galvanic isolation
of I/O-signals (2 groups x 8 inputs), to power supply and to interface Isolation voltage 500 VDC
Q.raxx D105
16 digital outputs
state, single or bit set, host controlled
High possible load
30 VDC / 500 mA short circuit proof
Short reaction time
10 µs up to 1 ms per input
Galvanic isolation
of I/O-signals (2 groups x 8 inputs), to power supply and to interface Isolation voltage 500 VDC
Q.raxx D107
6 configurable digital inputs
2 channels, each 3 differential or single-ended, frequency, counter, PWM, state
Adjustable threshold in 256 steps
Differential inputs in the range of -20 V up to + 20 V, Single-ended inputs in the range of 0 V up to +26 V
Frequency inputs
Frequency measurement up to 1 MHz (Chronos method), direction recognition
Counter
Up/down counter, quadrature counter with reference zero, up to 1 MHz
PWM inputs
Measurement of duty cycle and frequency, output with variable frequency and/or duty cycle
Galvanic isolation
Terminal 1, Terminal 2, power supply and interface Isolation voltage 500 VDC
Q.raxx C101
2 universal bridge input channels
Strain gage and inductive measuring bridges (full, half, quarter), LVDT
1 voltage or SSI input
Potentiometer, external function Generator or SSI Serial Interface for absolute Encoder or Temposonics®
4 digital inputs and outputs
Programmable logic for startup / shutdown sequencing and monitoring system status
1 servo drive output
Servo command signal, current or voltage, user-selectable ranges
System-on-a-chip computing
Powerful onboard computing for signal conditioning with a sample rate of 20 kHz and local closed-loop control
Pre-engineered or custom control loop on module
Pre-engineered force/position loop available or custom-designed control loop on the programmable DSP
Galvanic isolation
500C channel-to-channel-to-power for all analogue inputs